Damper Hall
of Shame

From government buildings and office blocks to universities and schools our engineers have come across faulty or poorly maintained fire and smoke dampers. Below are some examples of inoperable fire dampers and smoke dampers

Smoke Damper - failed

Smoke damper held open with wood as the actuator has failed

Wall construction - failed

Fire damper installed in incorrect location

access door covered - failed

Access door covered by other services and needs relocating

fire damper - failed

Electrical cables installed through fire damper making it impossible for the damper to close

fire damper - failed

Electrical basket and pipework installed through an air transfer fire damper

multiple issued - Failed

Incorrect fire damper installed, no fire stopping & no access door

ACCESS DOOR - Failed

Access door sealed over making visual inspection impossible

ACCESS DOOR - Failed

Construction of wall incomplete compromising the integrity of the fire damper